Example-1: For 11KV, Three Phase Motor. IR Value =11+1=12 MĪ© but as per IEEE43 It should be 100 MĪ©. Example-2: For 415V,Three Phase Motor. IR Value =0.415+1=1.41 MĪ© but as per IEEE43 It should be 5 MĪ©. As per IS 732 Min IR Value of Motor= (20XVoltage (p-p/ (1000+2XKW) IR Value of Motor as per NETA ATS 2007.
We need to get the next size wire: #6 AWG wire. This wire has a 65A ampacity and can handle 60 amps quite easily. Thatās why we use #6 AWG wire for 40 amp service 100 feet away. We also use #6 AWG wire for 40 amp service 150 feet away. When the sub panel is 200 feet away, however, we have to add 40% on top of the 50A minimum ampacity.
The cable hanging down is a big no-no. Quite sure you can't double up a breaker and quite possible if you think it is grounded you are mistaken, that neutral bus seems isolated from the panel (ground). The only way youāll get 208v is if your service is from 2 phases of a 3-phase electrical supply.
Jim_cliff11 said: Can I use a 240vac fuse in a 24vdc. In this case, I would say Yes you can use it. In general, the voltage rating on the fuse is there to prevent arcing after the fuse is blown. And of course, it is much "harder" to prevent arcing at DC circuit than AC. But additional details should be found on the fuse datasheet.
You wonāt have any problems as long as the 250V power cable fits into your 220V-240V wall power outlet and into the amplifier. Is 250V the same as 220V? 250V, 240V, 230V, 220V who cares, theyāre all āthe sameā thing ! Itās merely a ānominalā voltage for the insulation of the cable. Can I use a 250V plug on 220V?
mTQO.